毛细管网供冷室内环境对比实验研究

2019-10-08 08:47梁秋锦陈金华段坤林梁秋爽张波宋静
土木建筑与环境工程 2019年4期

梁秋锦 陈金华 段坤林 梁秋爽 张波 宋静

4.重庆电讯职业学院,重庆 402247 5.重庆远鉴旅游规划设计有限公司,重庆401120)摘要:对重庆地区毛细管网18℃供水温度下辐射供冷系统进行实验测试,分析了毛细管网顶棚、墙面、地面3种敷设方式室内热工参数。结果表明:毛细管网顶棚、墙面、地面3种敷设方式供冷稳定时,人员活动区的平均温度依次为26.27℃、27.22℃、26.57℃,辐射表面平均温度依次为20.96℃、21.14℃、22.76℃,PMV依次为-0.27、0.32、-0.2,PPD依次为7.06%、7.47%、6.34%。在实验条件下,3种敷设方式供冷时室内温度均能满足≤28℃的要求,PMV、PPD均能满足《民用建筑室内热湿环境评价标准GB/T50785 -2012》I级热舒适评价指标。

关键词:毛细管网;辐射供冷;敷设位置 PMV和PPD

中图分类号:TU831    文献标识码:A  文章编号:

4.Chongqing Telecommunication Polytechnic College,Chongqing 402247,China; 5.Chongqing Yuanjian Tourism Planning & Design Co. Ltd,Chongqing401120,China)Abstract: Tests of capillary radiant cooling system in Chongqing district were taken and thermal parameter were analyzed in conditions of three different capillary laying modes (ceiling, wall and floor) with 18℃ supply water temperature. It concluded that when capillaries were laid on the ceiling, wall and floor respectively, the average temperature of working area was 26.27℃, 27.22℃ and 26.57℃ respectively and the radiation surface temperature was 20.96℃, 21.14℃ and 22.76℃ in turn. By calculation, the PMV of three conditions was-0.27, 0.32 and -0.2 and PPD results were 7.06%, 7.47% and 6.34% respectively. It illustrated that all three laying ways at this experimental conditions could meet the air temperature requirements (no more than 28℃) and PMV, PPD attain thermal environment category I.

Key words: Capillary;Radiant cooling;Laying way;PMV and PPD

毛細管网作为一种新型空调末端形式,具有不占用室内空间、能与可再生能源结合及室内舒适度更高等优势,受到越来越多的关注。在能源成本越来越高、环境污染与温室效应加剧的大背景下,毛细管网的研究与应用越来越多。

国外,R.HOSEGGEN[1]等人针对顶棚供冷节能与舒适度进行实验研究,同时利用ESP-r软件进行模拟论证,结果表明:模拟结果与实验数据结果吻合。MIKESKA T[2]等人针对辐射供冷室内舒适性与供水温度关系进行研究,结果表明:当室内温度比供水温度高4 K时,室内温度舒适性较好。MELANIE F[3] 等人针对新型辐射顶棚通过实验实测与模拟进行性能测试,结果表明:新型辐射顶棚性能优于常规辐射顶棚。KEBLAWI A[4]等人针对顶棚供冷辅助新风系统,设计遗传算法控制器,可实现低能耗下满足同样的舒适度。LEE K G[5]等人针对地面辐射与对流空调系统通过实测对比分析,结果表明:辐射空调系统室内垂直温差较小。EUSEBIO Z.E[6]等人针对辐射与对流空调系统通过实验进行对比分析,结果表明:辐射空调系统室内舒适度好。KYU N R[7]等人总结分析了近50年辐射空调系统应用,得出辐射空调系统在节能性、舒适性方面不断改进优化的结论。

国内,李炅[8]等人针对毛细管网进行模拟研究,分析了毛细管网供冷能力影响因素。朱备[9]等人针对毛细管网辐射供冷表面结露进行研究,明确结合过冷度的运行策略。谢东[10]等人与王赟[11]等人均针对毛细管顶棚辐射供冷进行模拟研究,分析了顶棚辐射供冷时的供冷量。张金明[12]等人针对壁面辐射供冷与对流空调系统进行模拟研究,对比两种空调方式下室内热工参数。刘猛[13]等研究了不同供水温度与室外天气下毛细管网地棚供冷房间温度,供冷量与结露情况。李妍[14]等人分析了影响毛细管网的供冷能力相关曲线图。陈金华[15]等人针对毛细管网地面不同供水温度供暖研究室内参数,确定了供暖的最佳供水温度。陈露[16]等人针对毛细管网顶棚、墙面、地面进行模拟研究,分析了3种敷设方式舒适性。

通过文献查阅可知,针对顶棚、墙面、地面毛细管网的研究,均为理论计算与软件模拟,或只针对一种敷设方式进行实验研究。文章通过毛细管网顶棚、墙面、地面3种敷设方式实验研究。从室内人员活动区温湿度、壁面温度、室内垂直与水平温度、PMV、PPD等热工参数全面分析3种敷设方式毛细管网供冷的室内舒适性。

1实验系统介绍

1.1实验房间概况

实验地点为两间相同房间[17]如图1所示,房间410,房间412,每个房间的面积为21m2,尺寸为6m×3.5m×2.7m(长×宽×高),门洞的尺寸0.8m×2.1m(宽×高),外窗的尺寸2700mm×2000mm(宽×高);建筑外墙为实心砖墙(未做保温),厚度为240mm,内墙也为实心砖墙,厚度为200mm。窗户为单层玻璃窗,厚度为6mm,内设厚窗帘。

1.2实验系统

1.2.1 冷热源

该实验的冷热源为空气源热泵机组。冷热源与毛细管网末端中间设置换热水箱,通过换热水箱控制供水温度为18℃。原理图如图2所示。

1.2.2实验末端

实验的末端为顶棚、墙面、地面3种敷设方式,房间410顶棚、墙面敷设同侧供回S型毛细管网,房间412地面敷设同侧供回S型毛细管网。实验室建设时,为满足室内冷负荷需求,设置如下毛细管网参数见表1。

1.2.3新风系统 实验新风温度为24℃,相对湿度为60%,新风量为60m3/h,新风送风方式为上送风。

1.3实验内容

1.3.1测试方案 实验系统运行工况见表2,根据《辐射供暖供冷技术规程JGJ142-2012》中规定:毛细管网供水温度应保证供冷表面温度高于露点温度1℃ ~ 2℃。故本次实验在18℃供水温度下,测试毛细管网顶棚、墙面、地面3种敷设方式的室内热工参数。

1.3.2测点布置 实验测点[18]的布置原则参照《民用建筑室内热湿环境评价标准GB/T50785-2012》中的规定,详见图5、图6。实验数据采用实时监测,记录间隔为10min/次。

实验房间围护结构表面温度测点布置如下:顶棚布置5个,地面布置5个,左墙布置9个,右墙布置9个,外墙布置2个,内墙布置2个,共计32个。

实验房间空间温度测点布置如下:在图5中a、b、c、d、e位置上距地0.1m(脚踝)、0.6m(膝蓋)、1.1m(坐姿头部)、1.7m(站姿头部)、2.5m(房间上空)处,共计25个。空间湿度测点布置如下:在a、c、e位置距地1.1m高度处,共计3个。

1.3.3测试仪器 实验主要仪器如下表3所示:

2实验数据分析

2.1室外空气温度

实验期间室外逐时温度见图7。顶棚、墙面、地面3种敷设方式室外平均温度依次为29.97℃、31.26℃、29.97℃。

2.2室内人员活动区平均温度

人员活动区平均温度为a、b、c、d、e 五个水平位置分别距地0.1m、0.6m、1.1m、1.7m四个垂直高度的20个测点平均值。3种敷设方式实验期间人员活动区逐时温度见图8,由图可知:

1)毛细管网地面辐射供冷时,人员活动区温度达到28℃响应时间最长。顶棚、墙面、地面3种敷设方式响应时间依次为:20min、50min、60min。

2)3种敷设方式人员活动区平均温度均满足≤28℃要求,顶棚、墙面、地面3种敷设方式供冷稳定时人员活动区的平均温度依次为:26.27℃,27.22℃,26.57℃。

3)人员活动区温度的影响因素主要包括以下两个方面:辐射壁面温度与距辐射壁面距离。顶棚敷设毛细管网,由于其敷设构造较薄,辐射壁面温度低,因此供冷稳定时室内温度低于另外两种敷设方式;墙面敷设毛细管网,由于其敷设单面,冷空气横向传播速度慢,因此供冷稳定时室内温度高于另外两种敷设方式;地面敷设毛细管网,虽然其辐射壁面温度较另外两种敷设方式高,但是距离人员活动区最近,因此稳定时室内温度与顶棚敷设时温度接近。

2.3室内人员活动区平均相对湿度

人员活动区平均相对湿度为a、c、e点距地1.1m高度的相对湿度平均值,3种敷设方式人员活动区逐时平均相对湿度见图9,由图可知:

顶棚、墙面、地面3种敷设方式人员活动区稳定时平均相对湿度均满足室内舒适要求。墙面敷设人员活动区平均相对湿度略小于顶棚、地面。平均相对湿度依次为68.58%、64.13%、70.05%。

2.4露点温度分析

3种敷设方式露点温度见图10,由图可知:

顶棚、墙面、地面3种敷设方式的辐射壁面温度、附近空气温度均高于辐射壁面露点温度,因此实验过程中均未出现结露现象。但重庆地区湿度较大,为防止辐射供冷时出现结露,应设置通风除湿系统。

2.5辐射壁面平均温度

辐射壁面平均温度与毛细管网敷设构造密切相关。3种敷设方式辐射壁面逐时温度见图11,由图可知:

1)毛细管网敷设构造越薄,辐射壁面热响应时间越快,辐射壁面温度也越低。顶棚、墙面、地面敷设构造厚度依次递增,热响应时间依次递增,辐射壁面平均温度也依次递增,依次为20.96℃,21.14℃,22.76℃。

2)顶棚、墙面、地面3种敷设方式辐射壁面平均温度均满足《辐射供暖供冷技术规程JGJ142-2012》中的规定。具体要求值见表4。

3)常规地盘管地面上部敷设构造厚度较厚,不宜用于毛细管网地面,为缩短地面辐射热响应时间,降低辐射壁面温度,可降低毛细管网地面敷设构造厚度。

2.6围护结构壁面温度

3种敷设方式围护结构壁面温度分布见图13,由图可知:

1)3种敷设方式外墙温度高于其他壁面温度,由于外墙未做保温,故受室外温度影响较大。

2)墙面、地面敷设毛细管网供冷时,顶棚壁面温度均较高。主要原因是热空气在房间上部堆积,减弱顶棚壁面降温。

3)3种敷设方式辐射角系数对壁面温度的影响较小。

2.7空间垂直温度分析

3种敷设方式垂直温度分布见图14,站姿高差为0.1m~1.7m,坐姿高差为0.1m~1.1m。由图可知:

1)3种敷设方式供冷时,顶棚敷设垂直温差最小,且有“头凉脚暖”的感觉,舒适度最好。

2)3种敷设方式供冷时,坐姿或站姿纵向温差均小于1℃,满足ISO7730[19]推荐的小于2℃(A级)的温差。

2.8空间水平温度分析

室内空间水平温度分析选取a、b、c、d、e距地1.1m处温度。3种敷设方式水平温度分布见图15,由图可知:

1)墙面敷设毛细管网供冷时,水平温度分布最不均匀。为减弱单面墙供冷造成水平温度分布不均匀可两对面墙同时敷设。

2)顶棚、墙面敷设毛细管网供冷时,d点的温度出现温升的主要原因是该点位于门口,实验状况记录人员进出房间时将内走廊热量带入房间造成。

2.9 PMV、PPD分析

由图16、17可知:

1)顶棚、墙面、地面3种敷设方式供冷稳定时,PMV依次为-0.27,0.32,-0.2, PPD依次为7.06%,7.47%,6.34%。

2)3种敷设方式供冷稳定阶段时,室内PMV、PPD均满足《民用建筑室内热湿环境评价标准GB/T50785-2012》I级热舒适评价指标-0.5≤PMV≤0.5,PPD≤10%[17]。

3)3种敷设方式墙面辐射供冷时,室内舒适度最差。单面墙辐射供冷时,被降温的冷空气沿墙面下沉,在右墙下侧积聚,冷空气横向传递效果较差。因此墙面辐射供冷若想达到顶棚,地面辐射供冷效果,可通过增大毛细管网敷设面积、降低供水温度或增大管内流速等途径实现。

3结论

通过对比分析夏季毛细管网供冷室内环境,得出以下结论:

1)毛细管网供水温度设定为18℃时,3种敷設方式辐射供冷,室内人员活动区平均温度均满足≤28℃的要求。供冷稳定阶段,顶棚、墙面、地面人员活动区平均温度依次为26.27℃,27.22℃,26.57℃

2)毛细管网敷设构造越薄,辐射壁面热响应时间越快,辐射壁面温度也越低。顶棚、墙面、地面敷设构造厚度依次递增,热响应时间依次递增,辐射壁面平均温度也依次递增,依次为20.96℃,21.14℃,22.76℃。

3)顶棚敷设毛细管网供冷时纵向温差明显低于墙面、地面,舒适度更高。3种敷设方式纵向均小于1℃,满足ISO 7730推荐的小于2℃(A级)温差。

4)顶棚、地面敷设毛细管网供冷时室内水平效果接近,优于墙面。墙面敷设毛细管网供冷时,水平温度分布最不均匀。为减弱单面墙供冷造成水平温度分布不均匀可两对面墙同时敷设。

5)3种敷设方式室内预计平均热感觉指数PMV,预计不满意者百分数PPD均满足《民用建筑室内热湿环境评价标准GB/T50785 -2012》I级热舒适评价指标-0.5≤PMV≤0.5,PPD≤10%,供冷稳定阶段,顶棚、墙面、地面PMV依次为-0.27,0.32,-0.2,PPD依次为7.06%,7.47%,6.34%。

参考文献

[1] H?SEGGEN R, MATHISEN H M, HANSSEN S O. The effect of suspended ceilings on energy performance and thermal comfort[J]. Energy and Buildings, 2009, 41(2): 234-245.

[2] MIKESKA T, SVENDSEN S. Dynamic behavior of radiant cooling system based on capillary tubes in walls made of high performance concrete[J]. Energy and Buildings, 2015, 108: 92-100.[LinkOut]

[3] FAUCHOUX M, BANSAL M, TALUKDAR P, et al. Testing and modelling of a novel ceiling panel for maintaining space relative humidity by moisture transfer[J]. International Journal of Heat and Mass Transfer, 2010, 53(19/20): 3961-3968.

[4] KEBLAWI A, GHADDAR N, GHALI K. Model-based optimal supervisory control of chilled ceiling displacement ventilation system[J]. Energy and Buildings, 2011, 43(6): 1359-1370.[LinkOut]

[5] LEE K G, HONG W H. Thermal-environment characteristics and comfort of combined radiant-floor (Korean heating system ondol) and convective cooling system [J]. Journal of Central South University. 2013, 20 (12): 3589 – 3603.

[5] LEE K G, HONG W H. Thermal-environment characteristics and comfort of combined radiant-floor (Korean heating system ondol) and convective cooling system[J]. Journal of Central South University, 2013, 20(12): 3589-3603.[LinkOut]

[6] EUSEBIO Z. E, CONCECAON, MANUELA J R, et al. Evaluation of thermal comfort conditions in a classroom equipped with radiant cooling systems and subjected to uniform convective environment [J]. Applied Mathematical Modeling, 2011, 35(3): 1292-1305.

[7] KYU N R , KWANG W K . A 50 year review of basic and applied research in radiant heating and cooling systems for the built environment [J]. Building and Environment, 2015,91:166-190.

[8] 李炅,高珊,賈甲,等.毛细管辐射供冷系统性能的试验及数值模拟研究[J].制冷技术,2014,34(4):18-22.

LI J, GAO S, JIA J, et al. Experimental and

numerical simulation study on the performance of

capillary radiation cooling system[J] . Journal of Refrigeration Technology, 2014, 34

(4): 18-22.

[9] 朱备, 翟晓强, 尹亚领, 等. 毛细管辐射供冷的换热及结露特性的实验研究[J]. 制冷技术, 2013, 33(4): 5-10.ZHU B,ZHAI X Q,YIN Y L, et al. Experimental investigation of heat transfer and dew performances of capillary radiant cooling[J]. Chinese Journal of Refrigeration Technology, 2013, 33(4): 5-10.(in Chinese)

[10] 谢东, 王赟, 廖买利, 等. 基于不同管径毛细管辐射顶板供冷性能模拟[J]. 建筑热能通风空调, 2016, 35(11): 1-4,48.XIE D, WANG Y, LIAO M L, et al. Numerical modeling of cooling performance for capillary ceiling radiant cooling panel based on pipe diameters[J]. Building Energy & Environment, 2016, 35(11): 1-4,48.(in Chinese)

[11] 王赟, 谢东, 莫顺权, 等. 毛细管辐射冷却顶板供冷性能的数值模拟研究[J]. 制冷与空调(四川), 2016, 30(3): 287-290,294.WANG Y,XIE D,MO S Q, et al. Numerical modeling on cooling performance of capillary ceiling radiant cooling panel[J]. Refrigeration & Air Conditioning, 2016, 30(3): 287-290,294.(in Chinese)

[12] 张金明. 壁面辐射供冷与独立新风复合空调的数值模拟研究[D]. 西安: 西安科技大学, 2015. ZHANG J M. The numerical simulation research of the wall radiant cooling air conditioning system with independent fresh air[D]. Xi'an: Xi'an University of Science and Technology, 2015.(in Chinese)

[13] 刘猛, 王旭弟, Liu Meng, 等. 湿热地区毛细管地板供冷末端性能实测分析[J]. 土木建筑与环境工程, 2017, 39(1): 1-6.LIU M, WANG X D, LIU M, et al. Experimental analysis of terminal performance for floor cooling with capillary tubes in hot-humid area[J]. Journal of Civil,Architectural & Environmental Engineering, 2017, 39(1): 1-6.(in Chinese)

[14] 李妍, 许彬, 贾军华, 等. 毛细管网抹灰安装供冷能力分析[J]. 暖通空调, 2017, 47(1): 97-102.LI Y, XU B, JIA J H, et al. Cooling capacity analysis of capillary network with plasterer paving[J]. Heating Ventilating & Air Conditioning, 2017, 47(1): 97-102.(in Chinese)

[15] 陈金华, 杨雯芳, 沈雪莲, 等. 不同供水工况毛细管网地板辐射供暖实验研究[J]. 湖南大学学报(自然科学版), 2017, 44(11): 205-212.CHEN J H, YANG W F, SHEN X L, et al. Experimental research on capillary floor radiant heating in different water supply temperature[J]. Journal of Hunan University(Natural Sciences), 2017, 44(11): 205-212.(in Chinese)

[16] 陈露, 廖胜明, CHEN Lu, 等. 三种方式辐射供冷室内热环境对比分析[J]. 建筑热能通风空调, 2010, 29(3): 53-56.CHEN L, LIAO S M, CHEN L, et al. Three approaches to the comparative study of indoor thermal environment for radiant cooling system[J]. Building Energy & Environment, 2010, 29(3): 53-56.(in Chinese)

[17] 梁秋锦. 毛细管网不同敷设方式供冷性能研究[D]. 重庆: 重庆大学, 2017.LIANG Q J. Study on cooling performance with capillary different laying ways[D]. Chongqing: Chongqing University, 2017.(in Chinese)

[18] 陈金华, 梁秋锦, 李楠, 等. 毛细管网供暖室内环境对比实验研究[J]. 土木建筑与环境工程, 2018, 40(2): 88-94.CHEN J H, LIANG Q J, LI N, et al. Comparative experimental analysis of capillary radiant heating on indoor environment[J]. Journal of Civil,Architectural & Environmental Engineering, 2018, 40(2): 88-94.(in Chinese)

[19] ★★★, ★★★. Moderate thermal environments. Determination of the PMV and PPD indices and specification of the conditions for thermal comfort[S]. BSI British Standards, . DOI:10.3403/00814151

[20] GB 50736-2012《民用建筑供暖通風及空气调节设计规范》[S].北京:中国建筑工业出版社,2012.  GB 50736-2012 Regulations on the design of heating ventilation and air conditioning for civil buildings [S]. Beijing: China Architecture and Building Press, 2012.

(编辑:邓云)