钟文 姜丹
摘要:本文作者总结了某建筑住宅楼在主体施工期间发生不均匀沉降情况。对此,根据工程地质和现场施工条件,采用了压密注浆并辅以高压旋喷桩方法对地基持力层进行加固,消除地基隐患,提高地基土承载力。加固达到了预期目的。也取得了良好的经济效益。
关键词:压密注浆;高压旋喷桩;地基加固;施工技术
Abstract: in this paper the author summarizes the residential building a building in the construction period of the main body uneven subsidence occurred. To this, according to the engineering geology and the construction condition, the pressure grouting and dense with high pressure jet grouting pile for foundation strengthening method used, eliminate hidden dangers foundation, improve the bearing capacity of foundation soil. Strengthening the expected purpose is reached. Also achieved good economic benefit.
Key words: the pressure grouting carmel; High pressure jet grouting pile; Foundation reinforcement; Construction technology
中圖分类号:TU74文献标识码:A 文章编号:
一、工程概况
1.1概述
某建筑住宅楼层高7层,带半地下室,砖混结构,条形基础下部铺设有碎石垫层。在主体施工期间发现基础沉降速率过大,且为不均匀沉降。根据加固前的沉降资料,累计沉降量东北148mm,东南106mm,西北160mm,西南116mm。沉降差最大达55mm。
1.2工程地质条件
根据该场区工程地质勘察报告,与本工程有关的地层地质状况如下:
(1)填土:上部为棕色粉质粘土及建筑垃圾,下部以棕色粉质粘土为主,可塑~硬塑。层厚为0.3~1.6m。
(2)粉质粘土:棕色,土质均匀,疏松多孔,软~可塑,中~高压缩性,层厚为1.2~7.9m。该层土的标准承载力为100Kpa。
(3)粉质粘土:棕色,土质均匀,含Fe、Mn结核、岩屑,可塑,局部软塑,中压缩性,层厚为0.6~4m。该层土的标准承载力为1l0Kpa。
(4)粘土:棕红色,含少量Fe、Mn结核,硬塑~坚硬,中压缩性,层厚为2~10.5m。该层土的标准承载力为270Kpa。
地下水位埋深8.50m。
二、楼房不均匀沉降的原因分析
地基土为中~高压缩性软土,分布不均匀,基础位于软土上,地基承载力不足;在建设过程中,施工速度较快,加载过快,软土固化跟不上,地基土承载力下降,导致在主体施工期间即已产生较大的不均匀沉降。……