顺德地区10kV中性点经小电阻接地方式改造为智能型电抗器接地保护方式可行性研究探讨

2012-03-23 02:13:34麦灿波
城市建设理论研究 2012年4期
关键词:故障

麦灿波

摘要:智能型电抗器接地综合保护方式在佛山及广东电网已有成熟运行经验,能够根据单相接地故障的性质和类别采取不同的处理方法,对瞬时性故障在线消除,无须线路跳闸;对永久性故障可靠选线,可按照线路的特性选择恰当的时序适时切除。该保护方式具有明显的技术和经济优势,适用于供电线路为架空线路以及架空与电缆的混合线路的地区,能够同时满足供电安全性和供电连续可靠性需要,是改造顺德地区接地方式的最佳选择。

关键词:智能型电抗器接地保护方式消弧安全可靠性

中图分类号:U264.7+4文献标识码:A文章编号:

Abstract: intelligent reactor grounding in foshan and comprehensive protection way guangdong power grid has mature operation experience, can according to the nature of the one-phase ground fault take different categories and the processing method, almost to the online fault eliminate, need not line trip; Permanent fault location of reliable, can according to the characteristics of the circuit in choosing the right timing timely removal. The protection way has the obvious technical and economic advantages to apply to power lines for the overhead lines and overhead and cable hybrids area, can also meet the safety and reliability of power supply power supply continuous need, is reform in shunde grounding method of the best choice.

Keywords: intelligent reactor ground protection way away safety reliability arc

1. 顺德等地区10kV中性点经小电阻接地方式存在的问题

顺德供电局管辖的变电站大多数采用10kV中性点经小电阻接地方式,该接地方式属于大电流接地系统,发生单相接地时,能获得较大的阻性电流,直接驱动出线的零序保护动作于跳闸。其优点是能快速切除故障,过电压较低。其主要缺点是:1)不能区分瞬时性故障还是永久性故障,风吹草动都频繁动作于跳闸。2)对高阻接地故障存在误动和拒动。

1.1.线路频繁跳闸的危害

顺德地区供电线路主要为架空和电缆混合线路,并且是鼠害严重地区,在这些地区发生的单相接地故障绝大部分是瞬时性故障。据某供电所的不完全统计,该变电所辖区内三个10kV中性点经小电阻接地的变电站2010年线路跳闸约70次:由于雷雨影响的跳闸有36次,老鼠等小动物触碰有11次,草木及货车等非施工碰撞有7次;……