智能配电监控系统在广州白马大厦电房改扩建工程中的应用

2012-04-17 00:00:00蔡闻宇
城市建设理论研究 2012年35期

摘要:介绍在10/0.4KV配电系统中,加装智能电力仪表和变配电监控系统,对于主要回路的电压、电流、频率、功率因数、有功电能等电参量和开关信号进行实时采集;经组网远传至后台,从而实现对低压配电系统的电力状态实时监控和能耗监测。同时设置剩余电流式电气火灾监控系统,用于实时在线监测剩余电流,当达到设定值时,发出预报警信号,提醒工作人员排除故障隐患。关键词:变配电监控系统;RS485通讯;能耗监测;漏电火灾报警系统;

Abstract: In the 10/0.4KV distribution system, installation of intelligent power meter and power monitor and control system for the main circuit, the voltage, current, frequency, power factor, active power of electric parameters and the switch signal acquisition; by far to the network background, which is of low voltage distribution system power state real-time monitoring and energy consumption monitoring? While installing the residual current fire monitoring system, used for real-time monitoring of residual current, when reaches the set value, send out alarm signal, to remind staff of troubleshooting problems.

Key words: power monitors and control system; RS485 communication; energy consumption monitoring; electric leakage fire alarm system;

中图分类号:TM421 文献标识码:A 文章编号:

0 概述广州白马大厦建筑面积约5.8万㎡,地下1层,地上9层,地下1层为停车场,设备机房,管理用房使用;地上部分主要作为商铺及配套用房使用,属于一类高层公共建筑,耐火等级为一级。根据配电系统管理和能耗监测的要求,需对该大厦电房改扩建工程涉及的配电柜进行智能化管理及监控,以提高管理水平,降低劳动强度成本。同时保证电力系统的可靠性及运行、检修的方便,配变配电智能化管理及监控系统(带UPS)采用分层分布以太网结构,分为站控层、通讯管理层、间隔层。

本项目实际要监控内容包括智能化电力监控系统和漏电火灾监控报警系统。

电力监控系统设计

在地下一层配电房内的主变低压进出线柜、低压母联柜、市电、发电机切换柜、发电机进线柜和其他低压馈线回路设置三相数字式多功能测控电表116台,测量一回线路的全部三相电量:U、I、P、Q、Cosφ、kWh、kVarh、f等;在配电房内的低压馈线回路设置单相数字式多功能测控电表37台,测量一回线路的单相U、I、P、Q、Cosφ、kWh、kVarh、f等;……