吴伟康
摘要:本文采用Pile 7.1桩基础设计计算软件计算沉降,在不均匀沉降满足设备要求的情况下,对筏板厚度及桩基布置进行优化。结合工程经验,采用双层埋件,减小埋件施工误差控制的难度,并根据1000kV GIS设备基础的特点,采取各种措施减小大体积混凝土施工的影响及基础表面的温度裂缝。
关键词:GIS;筏板基础;不均匀沉降;施工误差;大体积混凝土;温度裂缝
Design Study of GIS Foundation
Wu Weikang
(Tongji University Shanghai 200092)
ABSTRACT: This paper uses the Pile 7.1 pile foundation design and calculation software for computing settlement. While the asymmetry settlement satisfying the requirement of the 1000kV GIS equipment, the thickness of raft foundation and pile layout is optimized. According to the engineering experiences, double embedded parts is used to reduce the construction error control difficult, and various measures was taken to reduce the influence of the mass concrete construction and the base surface thermal crack.
KEYWORDS: GIS, raft foundation, asymmetry settlement, construction error, mass concrete, thermal crack
前言
由于1000kVGIS设备重要性极高,对沉降变形极为敏感,为保证设备的顺利安装、正常运行及使用,厂家对GIS设备基础提出的不均匀沉降、施工误差等要求均较常规工程高。
本文主要从设计的角度出发,通过调整桩位布置、基础筏板厚度来控制差异沉降,采用双层埋件,减小施工难度,利用板上电缆沟对上部基础进行划分,形成一个个独立的支墩,基础表面除配置温度钢筋外,设置适当的缩缝与分隔缝,减小基础不规则等所产生的裂缝。
1、基础沉降控制
1000kV GIS设备基础的允许沉降差如下:
(1) GIS本体基础中两个独立的基础大板的不均匀沉降差不大于20mm。
(2) 进出线套管基础与GIS本体大板基础之间的沉降差值不大于25mm。
(3) 每一块大板基础上的任意两块埋件的沉降差随埋件间距离的不同而不同:埋件间距D≤20m时,沉降差应≤1‰;埋件间距D>20m时,沉降差应≤1‰,且≤30mm。
由于GIS设备基础重要性高,沉降变形敏感,结合地质情况,采用桩筏基础,选用PHC 400 AB 95-23预制管桩,以⑥1暗绿色粉质粘土层作为桩端持力层。考虑到远景扩建时对运行设备的影响,桩基施工按终期规模考虑。……p>