中压开关柜典型故障因素及防范处理

2017-08-09 19:53:15常家森路浩曹裕群施翔周永
中国科技纵横 2017年13期
关键词:故障

常家森++路浩++曹裕群++施翔++周永军

摘 要:随着配电网的快速发展,中压开关柜在电力系统中用量大增,运行中故障也越发常见,影响供电可靠性。本文分析了故障因素,归纳提出相应的防范处理措施,有利于保证设备和人员生命安全,提高供电可靠性。

关键词:开关柜;故障;防范处理

中图分类号:TM89 文献标识码:A 文章编号:1671-2064(2017)13-0083-02

Typical Fault Elements and Prevention Treatments of Medium Voltage Switch Cabinets

Chang Jiasen,Lu Hao,Cao Yuqun,Shi Yang,Zhou Yongjun

(Zhongtian Electrical Technology Co., Ltd., Nantong Jiangsu 226463)

Abstract:As the rapid development of distribution network, the amount of medium voltage switch cabinets used in the power system increases greatly, and faults in operation get more and more common and affect the reliability of power supply. In this paper, fault elements were analyzed, and corresponding prevention treatments were concluded. This work is beneficial for assuring the safety of equipment and staff and increasing the reliability of power supply.

Key words:switch cabinet; fault; prevention treatment

10~35kV配电开关柜在电力系统中大量使用,运行中经常会发生电气故障,造成物质和经济损失。随着电网不断扩大和对供电可靠性要求不断提高,加强对配电设备运行故障的原因分析及预防处理,对加强设备保护,有效降低故障发生时设备的损坏程度,保证设备的长期安全运行有重要意义。

1 开关柜故障因素

通常中压开关柜分为半封闭式和全封闭式,前者如GG-1A(F)、GSG-1A(F)等,后者如JYN、KYN、XGN等,按断路器型号分为真空开关柜、少油开关柜、SF6开关柜等。由于开关柜型号较多,综合了断路器、负荷开关、接触器、高压熔断器、隔离开关、接地开关及所用变以及控制、测量、保护、调节装置,内部连接件、附件、外壳和支持件等元器件及组件,各个环节都可能引起缺陷和故障。归纳起来,故障因素大致有以下几种。

1.1 机械故障

机械故障包括机构拒动、误动故障和断路器本体开断关合故障。拒动、误动故障是开关柜最主要的故障,原因分两类:一类是由操动机构和传动系统机械故障造成,包括机构卡涩,部件变形、位移或损坏,分合闸铁芯松动、卡涩,轴销松断,脱扣失灵等;……