110kV洪钟变电站通风降噪优化设计研究

2017-10-21 16:01:40张旻
价值工程 2017年32期

张旻

摘要: 本文通过对110kV洪钟变电站类型及其所处地理位置、周围敏感点等情况的综合考虑,具体分析噪声源及特性,从声源控制、传声途径控制、合理建筑结构和隔声、吸声设计、环境污染及防护等几个方面提出变电站通风降噪方法,为提高变电站运行维护水平建言献策。

Abstract: Based on comprehensive consideration of the type, geographical location and surrounding sensitive points of 110kV Hongzhong substation, this paper analyzes the noise source and characteristics, and proposes ventilation and noise reduction methods from sound source control, acoustic path control, reasonable building structure and sound insulation and suction design, environmental pollution and protection, in order to improve the level of substation operation and maintenance.

关键词: 变电站风机;噪声源及特性;通风降噪

Key words: substation fan;noise source and characteristic;ventilation and noise reduction

中图分类号:TU831.8 文献标识码:A 文章编号:1006-4311(2017)32-0131-02

1 变电站噪声

1.1 站址概况 拟选110kV洪钟变电站位于厦门市翔安区后房社区。110kV洪钟变配电装置楼总建筑面积1028m2。一层建筑面积1028.00m2,层高4.0m,主要功能房间为10kV 配电室,电容器室,二次设备室,110kV GIS配电室(挑高8.0m),#1、#2、#3主变压器室(挑高8.0m)及户外散热器。

1.2 变电站通风系统及噪声构成 110kV洪钟变电站的主变室、站用变室、电容器室、电抗器室采用墙上低位百叶窗自然进风,高位轴流风机机械排风的通风系统来排除室内余热,另设事故排风机兼作正常通风系统的排风机用。110kV GIS室设置自然进风、机械排风的通风系统,吸风口设在GIS室的房间下部,排除室内可能存在的SF6 气体,事故排风由下部正常排风系统和上部排风系统共同来保证。根据辐射噪声的特点,风机噪声主要由下述四部分组成:①风机运行时进、排风口产生的空气动力性噪声;②机壳、管壁以及电动机轴承等发出的机械性噪声;③电动机的电磁噪声;④运行的风机与基础连接处发生振动而产生的高频辐射噪声。

1.3 风机噪声源分析 轴流风机的噪声可以分为两种类型,一是空气动力性噪声,二是电磁噪声,并且前者是主要的噪声。……

登录APP查看全文