杨亚炬
摘 要:三代核电厂的安全系统采用非能动安全理念,使其电气系统简化,设备减少,更便于操作;延长了安全相关的1E级直流及UPS系统供电时间,提高了电厂运行的安全性。文章针对某三代核电厂1E级直流及UPS系统蓄电池的设计要求,介绍了1E级蓄电池的试验内容,对后续核电站1E级蓄电池的调试有一定的参考价值。
关键词:核电站;IDS系统;调试;蓄电池;工作周期
中图分类号:TM623.3 文献标志码:A 文章编号:2095-2945(2018)36-0048-02
Abstract: The safety system of the third generation nuclear power plant adopts the passive safety concept, which simplifies the electrical system, reduces the equipment and makes the operation more convenient, prolongs the power supply time of 1E class DC and UPS system related to safety, and improves the operation safety of the power plant. According to the design requirements of 1E-stage DC and UPS batteries in a three-generation nuclear power plant, this paper introduces the test contents of 1E-stage batteries, which has certain reference value for the commissioning of 1E-stage batteries in subsequent nuclear power plants.
Keywords: nuclear power plant; IDS system; commissioning; storage battery; working cycle
引言
与一般压水堆核电厂相比,三代核电的安全系统采用非能动安全理念,使电厂电气系统得到简化,不需要1E级的交流电源系统和应急柴油发电机,供电系统的接线及其装置更加简单,更便于操作。其安全相关电源系统由不接地的1E級直流及UPS系统(IDS系统)提供,延长不间断供电时间,提高了电厂运行的安全性。因此要求IDS系统蓄电池延长不间断供电时间,以提高了电厂运行的安全性。本文简要介绍了某三代核电的IDS系统蓄电池的设计要求,并结合工程实践介绍1E级蓄电池的试验内容。
1 IDS系统蓄电池组设计要求
1E级直流及UPS系统是全厂唯一的1E电源,在所有厂内厂外交流电源不可用时,1E级蓄电池向相关需持续运行的负载提供电源,其主要能成与功能如下:
(1)IDS包括A、B、C、D 4组独立的蓄电池系统。4组蓄电池系统中任何3组都能实现安全停堆,并将核电厂维持在安全停堆状态。
(2)在设计基准事件(包括失去所有交流电源)后,任何一组A和D组蓄电池系统的容量至少能向选定的安全相关设备供电24h,B和C组蓄电池系统的容量能向选定的安全相关设备供电24h或72h。……