一起典型电压切换回路接线错误的原因分析

2018-09-13 10:47:16王波孙仪贾伟麦立
科技创新与应用 2018年23期
关键词:交流

王波 孙仪 贾伟 麦立

摘 要:双母线接线方式中电压切换装置能够实现电压回路的自动切换,从而为保护、测量、计量提供正确的电压来源。文章结合现场运行中发生的一起电压切换回路接线错误,分析了电压切换装置的原理和重要性,有助于提高运维人员发现问题的能力和专业技能。

关键词:电压切换;双母双分段;CZX-12R型操作箱;辅助接点

中图分类号:U224.2+7 文献标志码:A 文章编号:2095-2945(2018)23-0040-02

Abstract: The voltage switching device in the double bus connection mode can realize the automatic switching of the voltage loop, thus providing the correct voltage source for protection, measurement and metering. This paper analyzes the principle and importance of voltage switching device, which is helpful to improve the ability and professional skills of operation and maintenance personnel to find out the problems, in relation with a voltage switching loop wiring error occurred in the field operation.

Keywords: voltage switching; double bus and double section; CZX-12R type operation box; auxiliary contact

1 電压切换回路的原理与作用

1.1 作用

双母线系统上所连接的电气元件,为了保证其一次系统和二次系统在电压上保持对应,要求保护、测量、计量都有自动切换功能。保护及自动装置的二次电压回路随同主接线一起进行切换,以免发生保护或自动装置误动、拒动。自动切换通过用隔离开关辅助触点去启动电压切换中间继电器,利用其触点实现电压回路的自动切换来实现。

1.2 原理分析

图1为CZX-12R型操作箱的原理图,其中1YQJ4、1YQJ5、1YQJ6、1YQJ7、2YQJ4、2YQJ5、2YQJ6、2YQJ7为双位置继电器,一个线圈得电后,即使切换回路电压消失,继电器仍保持原来状态,直到另一线圈得电后才转换为另一种状态。1YQJ1、1YQJ2、1YQJ3、2YQJ1、2YQJ2、2YQJ3为非保持型继电器,即在线圈带电时继电器常开接点闭合,常闭接点断开。1G、2G分别为I母和II母母线侧刀闸辅助接点,当线路在I母运行时,1G常开接点和2G常闭接点闭合,1G常闭接点和2G常开接点断开。1G接点闭合,1YQJ1、1YQJ2、1YQJ3继电器动作,1YQJ4、1YQJ5、1YQJ6、1YQJ7继电器也动作且保持,指示灯1XD亮,表示电压取自I母电压互感器。II母刀闸的常闭接点将2YQJ4、2YQJ5、2YQJ6、2YQJ7复位。1YQJ6、1YQJ7继电器动作后,其常开接点闭合,I母A、B、C三相电压供线路保护或测控装置用。……

登录APP查看全文

猜你喜欢
交流
如此交流,太暖!
科教新报(2022年12期)2022-05-23 06:34:16
学习交流
加强交流沟通 相互学习借鉴
今日农业(2021年14期)2021-10-14 08:35:28
学习交流
学习交流
学习交流
学习交流
周樱 两岸交流需要更多“对画”
海峡姐妹(2020年8期)2020-08-25 09:30:18
回眸·交流
遵义(2018年14期)2018-08-06 06:32:18
交流&イベント