蒸气压缩循环蒸发冷却式冷水热泵机组用于商业建筑的经济性研究

2018-09-14 10:54:24程嘉颖陈刚
科技创新与应用 2018年21期

程嘉颖 陈刚

摘 要:作蒸发式冷凝机组应用于商业建筑的前景分析。基于某工程实例,介绍了该机组在夏季制冷工况下的设计思路,并根据当前市场上生产厂家提供的数据,分析了初投资、运行费用和维护费用,以计算投资回收期。结果表明,蒸发式冷凝机组能有效节省运行能耗,并且相对于常规水冷机组,其投资回收期分别为3.9年(含螺杆式压缩机)和5.4年(含磁悬浮离心式压缩机)。

关键词:蒸发式冷凝机组;商业建筑;性能系数;运行能耗;空调;制冷

中图分类号:TB65 文献标志码:A 文章编号:2095-2945(2018)21-0055-03

Abstract: The application prospect of evaporative condensing unit in commercial buildings is analyzed. Based on an engineering example, the design idea of the unit under summer refrigeration condition is introduced, and the initial investment, operation cost and maintenance cost are analyzed according to the data provided by the manufacturers in the market at present, in order to calculate the payback period of the investment. The results show that the evaporative condensing unit can effectively save energy consumption, and the investment recovery period is 3.9 years (including screw compressor) and 5.4 years (including magnetic suspension centrifugal compressor), respectively, compared with the conventional water cooling unit.

Keywords: evaporative condensing unit; commercial building; coefficient of performance; operational energy consumption; air conditioning; refrigeration

引言

近年來我国建筑面积持续增长[1],建筑的运行能耗巨大[2],因此解决建筑节能已成为我国节能减排的一项重大问题[3,4]。蒸气压缩循环蒸发冷却式冷水(热泵)机组(以下简称“蒸发式冷凝机组”),是将空调系统中的常规空调水冷机组的冷凝器和冷却塔集成,具有传热系数高、冷凝温度低,可以节省系统能耗的特点。以某一工程为例,本文对该机组作经济性分析,并计算其投资回收期,以探讨其应用于商业建筑的前景。

1 工程概况

该商业项目位于南京,地处夏热冬冷地区,总建筑面积约14万m2,其中商业建筑面积为90316m2。

该地区不考虑峰谷电价。

2 技术分析

2.1 冷负荷计算与冷源选型

根据商业建筑面积(90316m2),估算系统冷负荷为2750 RT(合9670kW)。

笔者收集了当前市场上生产蒸发式冷凝机组的9家厂家的资料,发现当前市场上的蒸发式冷凝机组,可根据换热器类型分为板管式换热器和降膜式换热器,其系统SCOP分别为4.8和5。……