保安电源进线开关双位继电器的改造与思考

2018-12-07 01:54:52蒋锋
中小企业管理与科技·中旬刊 2018年9期

蒋锋

【摘 要】论文针对某厂一起由保安电源进线开关双位继电器引起的保安段运行异常及相关改造案例进行分析,从事件经过、情况分析、暴露问题、采取措施、改造效果逐步推进,详细说明了此次异常的核心问题所在以及改造过程与改造效果。针对两种不同的继电器,通过试验,以具体数据进行比较,最终得出电磁式继电器更适合保安进线开关的结论,同时针对电气元件的选型问题进行思考。

【Abstract】The paper analyzes the abnormal operation of the security section caused by the two position relay of the inlet line switch of the security power supply in a certain factory, and the related reconstruction cases. The core problems of this anomaly and the transformation process and effect are explained in detail from the incident passing, situation analysis, exposure of problems, the measures taken, transformation effect. In view of the two different relays, the concrete data are compared through experiment. Finally, the conclusion that the electromagnetic relay is more suitable for the safety wire inlet line switch is concluded, and the selection of electrical components is considered at the same time.

【关键词】保安段;双位继电器;电磁式

【Keywords】 security section; two position relay; electromagnetic type

【中图分类号】TM761 【文献标志码】A 【文章编号】1673-1069(2018)09-0145-02

1 引言

在电厂中,保安电源系统是厂用电系统中最重要的一道防线[1],保安电源必须在系统发生事故等异常情况下给机炉设备和重要的电气设备提供正常的工作电源。正因如此,保安电源系统的稳定运行与正常切换显得至关重要。

2 事件经过

2017年6月6日,某厂运行人员巡检时发现汽机保安MCC2段的工作进线开关和备用进线开关均处于合位状态,即两路进线开关处于合环状态,且保安MCC2段工作进线开关在DCS上的显示状态和就地状态不一致,就地为合位,DCS上显示分位。(保安MCC2段系统图如图1所示)

3 情况分析

经调取220kV故障录波突变量记录发现,6月6日17时38分220kV系统侧电压Ua,Ub有瞬间抖动,Ua,Ub二次电压降低,Ua降低幅度最大,二次幅值降到34V左右,100毫秒内系统电压恢复。当时#2机停机,保安MCC2段电源最终取自启备变,与系统关系比较紧密[2]。受系统电压抖动影响,6kV1段母线电压,保安MCC母线2段电压有瞬时降低的现象。……