张琨 周浩

【摘 要】电厂内部分低压电动机运行功率较大,多次出现因启动瞬间产生大电流对接地保护电流互感器采样回路造成干扰,增大测量误差,导致接地保护继电器误动作事件。通过对电磁干扰和抗干扰措施的分析,提出提高电流互感器测量精度的改进方案,避免低压电动机启动引起接地保护误动。经过数据测量和现场验证,改进方案可在电厂应用和推广。
【关键词】低压电动机;干扰;接地保护;误动
Abstract:some low-voltage motors in the power plant have large operating power,and the sampling circuit of the ground protection current transformer caused by the large current generated at the moment of starting causes interference,increases the measurement error,and leads to the misoperation events of the grounding protection relay. Based on the analysis of electromagnetic interference and anti-interference measures,this paper puts forward an improved scheme to improve the measuring accuracy of current transformer and avoid the misoperation of grounding protection caused by the start of low-voltage motor. After data measurement and field verification,the improved scheme can be applied and popularized in power plant.
Key words:low-voltage motor interference grounding protection misoperation
低压电动机作为转动部件,在电厂广泛应用,可连接风扇、泵体等设备。低压大容量电动机在单相绕组发生短路接地故障时,其上游熔断器熔断时间过长,不利于安全运行,因此需增设后备接地保护,在故障发生时,迅速动作切断电路。
电厂大容量低压电动机启动瞬间产生的启动电流可达电动机额定运行电流的数十倍。对于启动电流对接地保护电流互感器采样回路形成干扰,增大测量误差,导致接地保护误动作问题,需对干扰的形成进行深入分析,制定切实有效的抗干扰改进措施。
一、问题与现状
1.1典型事件