针对AGC模式的自动控制策略优化

2019-10-21 19:08:22朱策
中国电气工程学报 2019年10期

朱策

摘要:超超临界直流炉机组在AGC模式下往往难于满足电网要求,其主要原因在于该类机组蓄热能力较小,初始的响应速度慢。针对机组特点,通过对其协调控制系统进行优化改进,以满足电网调度的要求,并在频繁的AGC变负荷工况下减小机组的汽压、汽温的变化幅度。

关键词:AGC;CCS;协调控制;控制策略优化

Abstract:The unit with ultra-supercritical once-through boiler under AGC mode is often difficult to meet the requirements of the power grids .The main reason is that this kind of unit cannot store much energy and the response speed of the initial is slow .Based on this characteristics of unit, This pager gives some suggestions and optimizations to improve the coordinated control strategy,in order to meet the requirements of power grid dispatching ,and the changing of steam pressure and temperature of the unit can be reduced during frequent load change under AGC.

Key words:AGC;CCS;cordinated control;control strategy optimization

隨着时代和科学技术的发展,我国新建机组大部分是超超临界机组。由于近几年电网对供电质量标准越来越高,要求电厂在AGC控制(尤其是联络线模式)下能够满足要求,这就需要电厂具有足够的响应速度和适应能力。

通过改进优化控制策略以提高机组性能,特别是在AGC变负荷指令频繁波动的情况下尽可能减小机组的汽压、汽温波动幅度。对机组安全稳定运行和满足电网要求是很有意义。

一、优化原因分析

(一)AGC指令

AGC指令存在频繁来回小幅波动及大幅度单向变负荷后未等机组稳定马上反向变负荷两种情况,这对机组调节极其不利,容易造成汽压、汽温的偏差大甚至失衡,发电负荷无法跟随AGC负荷指令,严重时甚至需要退出AGC控制。

(二)协调控制系统缺乏专门应对AGC模式的策略

对于AGC方式和CCS方式来说,机组的锅炉、汽机控制并无区别,区别在于机组负荷指令分别由调度和运行人员给出。由于运行人员手动给出负荷指令时往往会考虑机组运行工况,而且通常其给出的指令变化较少且幅度较大,便于锅炉微分前馈起作用,故在CCS模式下机组运行平稳且性能良好。……

登录APP查看全文