张雨默 刘强 金婷 李伟 李德锋



摘要:随着信息技术的不断发展,大数据、云计算、人工智能等前沿技术蓬勃发展,IDC数据中心作为重要的基础设施,支撑着新兴技术的运行应用,IDC数据中心电源系统作为数据中心运行的动力“心脏”,运行的稳定性直接影响业务的稳定性。本文针对IDC电源系统中典型设备ATS(自动转换开关)的一起故障进行分析,详细分析了故障原因并总结了维护要点。
关键词:数据中心;电源系统;ATS;维护要点
中图分类号:TM762.1:文献标识码:B
Fault analysis of ATS local overheating during switching of IDC power supply and distribution system
ABSTRACT:With the continuous development of information technology, big data, cloud computing, artificial intelligence and other cutting-edge technologies are booming. As an important infrastructure, IDC data center supports the operation and application of emerging technologies. As the power "heart" of data center operation, IDC data center power system directly affects the stability of business. This paper analyzes a fault of ATS (automatic transfer switch), which is a typical equipment in IDC power supply system. It analyzes the fault causes in detail and summarizes the maintenance points.
KEY WORDS: IDC; Power system ; ATS; maintenance points
ATS(自動转换器)是一种用于自动转换两路电源供给负载使用,将负载电力供应从一个电源自动转换至另一个电源,保证负载供电连续,可靠运行1,目前工程上常用的ATS主要有PC级与CB级两类,PC级ATS为电磁驱动式,具有转换速度快
随着供电系统规模不断扩大,供电系统结构日趋复杂2,ATS使用场景及使用频率增多,产生了一些新的故障类型3,4。本文结合ATS使用维护过程中发现的一次典型故障,通过理论分析与现场实际测试,总结研究了此次故障的原因并为ATS的维护提供了一些建议。
1 故障现场
某数据中心低压配电系统大面积使用某知名品牌ATS,在进行巡检过程中连续出现ATS切换时单项瞬时过热问题。
三列低压柜之间组网架构如图所示,低压柜之间通过母联柜进行备用切换,ATS作为应急状态下外接车载油机切换作用。
当对B列巡检时,通过母联柜将B列后端负载切换至C列,准备对B列设备进行停电巡检作业,此时C列ATS负荷为B列负荷与C列原有负荷之和。……