摘要:转子绕组匝间短路严重影响发电机的安全稳定运行。本文针对某电厂600MW汽轮发电机转子匝间短路故障进行深入分析,通过测量转子直流电阻、交流阻抗试验以及RSO试验等多种试验方案,分别进行诊断,最终得出该发电机转子匝间短路属于不稳定匝间短路,文中制定了具体治理方案,以供国内相同类型机组发电机转子相同类型故障借鉴参考。
關键词:发电机;转子匝间短路;RSO试验;转子交流阻抗试验
The Fault Case Analysis Of The Rotor Turn-To-Turn Short Circuit Fault Of 600Mw Turbine Generator
Yang Wenguang
(Zhuhai Urban Construction Smart Energy Co., Ltd, Zhuhai, Guagndong Province 519000)
ABSTRACT: The short-circuit of the rotor winding turns seriously affects the safe and stable operation of the generator. This paper makes an in-depth analysis of the short-circuit fault between the rotors of a 600MW turbogenerator in a power plant, through the measurement of the rotor DC resistance, AC impedance test and RSO test and other test plans, respectively diagnoses, and finally draws the generator inter-turn short circuit It belongs to unstable inter-turn short circuit, and a specific treatment plan is formulated in this paper for reference for the same type of generator rotor faults of the same type in China.。
KEY WORD: Generator;The Rotor Turn-To-Turn Short Circuit;RSO test;Rotor AC impedance test
1 前言
600MW汽轮发电机型号为QFSN-600-2,上海汽轮发电机厂生产,出厂编号为60SH014。2004年5月出厂,2006年1月投产,2007年3月进行第一次大修,2013年10月进行第二次大修,在此次大修期间在进行发电机转子电压分布试验时发现两级电压分布不均匀。
2 转子匝间故障诊断
针对该发电机转子匝间故障的诊断,试验人员采用转子直流电阻测试、膛外交流阻抗试验、极平衡、电压分布试验、RSO试验等方法分别对发电机转子进行测试。
2.1 转子直流电阻测试
转子直流电阻测试标准为与初次(交接或大修)所测结果比较,在相同温度下,其差别一般不超过2%。发电机转子直流电阻测试结果为合格,详见表1。
2.2 转子膛外交流阻抗试验
膛外交流阻抗试验标准是在相同试验条件下与历年试验数值比较,不应有显著变化(发电机厂规定偏差10%),发电机转子膛外交流阻抗试验结果合格,详见表2。
2.3 极平衡和RSO试验
极平衡和RSO试验标准为两极波形偏差小于200mV。试验结果超出《JB/T8446-2005隐极式同步发电机转子匝间短路测试方法》中“各极线圈间的电压差不得大于最大值的3%”标准,结果详见表3。……