孙立国 梁修华 朱小灿


【摘 要】针对某核电厂3号机组6.6 kV配电系统断路器无法分闸的问题,对断路器的扭簧位置、油脂干枯情况等进行分析,结果表明断路器分闸驱动机构卡涩是故障的根本原因,据此制定了针对性的处理措施并优化维修策略。
【Abstract】In view of the problem that the circuit breaker of 6.6 kV distribution system of unit 3 in a nuclear power plant cannot be opened, the position of the torsion spring of the circuit breaker and the situation of grease drying are analyzed. The results show that the jamming of the opening driving mechanism of the circuit breaker is the root cause of the fault. Based on this, targeted treatment measures and maintenance strategy are formulated.
【关键词】断路器;分閘;卡涩;扭簧
【Keywords】circuit breaker; opening; jam; torsional spring
【中图分类号】TM561 【文献标志码】A 【文章编号】1673-1069(2020)06-0153-02
1 引言
某核电厂3号机组大修期间,在执行6.6 kV配电盘(LGB)从厂用变压器A(简称厂变)供电切换至辅助变压器(简称辅变)供电试验(T3LGB001)时,其断路器(LGB001JA)未按预期自动分闸,导致厂用配电盘(LGB)失电,A列应急柴油发电机(LHP)自动启动并带载厂用应急配电盘(LHA)。现场检查发现,LGB001JA分闸线圈短路,直流供电开关跳闸。
本文通过对LGB001JA的分闸原理、机械机构、分闸线圈及受力情况等进行分析,发现该核电厂1~6号机组约150台同型号断路器均存在类似的故障模式。
2 LGB001JA倒电过程与分闸原理简介
2.1 倒电过程
LGB001JA为母线正常进线断路器,在LGB母线失压的情况下(电压低于70%额定电压)存在倒电逻辑,以确保迅速恢复厂用电源,保障机组的正常运行。厂用电源向辅助电源切换逻辑有以下3种:①快速倒电(0s):由汽轮机保护系统触发且500kV高压出口断路器全部断开。②一级慢速倒电(1.2s):由LGB/LGC母线低电压保护触发,且同步并网系统断路器(GSY001JA)(或LGA001JA)断开,断路器LGB001JA合闸,延时1.2 s发出LGB001JA断开指令,LGB001JA成功断开0.5 s后,LGB102JA合闸。③二级慢速倒电(5s):由LGB/LGC母线低电压保护触发,延时5s发出LGB102JA合闸指令。T3LGB001试验是检查LGB配电盘从厂变供电自动切换到辅变供电的性能的操……