探讨改善共箱封闭母线绝缘问题的应急和长效措施

2020-12-21 03:46:46陈志洋
中小企业管理与科技·上旬刊 2020年12期
关键词:改善

【摘  要】积极改善共箱封闭母线绝缘问题至关重要,这关系到了机组和电厂用电的安全稳定运行。论文以某沿海600MW电厂为例,针对性地分析了改善共箱封闭母线绝缘问题的应急和长效措施,具有很强的实践性、操作性,以供他人参考借鉴。

【Abstract】It is very important to actively improve the insulation problemof  the common box closed busbar, which is related to the safe and stable operation of the unit and the power plant.Taking a coastal 600MW power plant as an example, this paper analyzes the emergency and long-term measures to improve the insulation problem of common box closed busbar, which has strong practicality and operability for others to use for reference.

【关键词】改善;共箱封闭母线;绝缘

【Keywords】improvement; common box closed busbar; insulation

【中图分类号】TM645.1                               【文献标志码】A                                   【文章编号】1673-1069(2020)12-0166-02

1 引言

共箱封闭母线广泛应用于大型发电机组厂用变压器低压侧与高压配电装置之间的电流传输。沿海的电厂由于长期处于高盐密环境,容易造成封闭母线的密封性能下降,空气相对湿度较大,母线绝缘情况也随之劣化,严重时将导致母线接地、短路跳闸,威胁机组的安全运行。某600MW电厂地处沿海,其厂用6kV共箱封闭母线使用DMC材料绝缘件,采用伴热带加热方式驱潮,但因共箱母线长,伴热带功率小,驱潮效果差且耗时长。机组或启备变检修送电前,如若遇上潮湿、雨水天气,母线绝缘常遇到不合格的情况,直接影响到设备正常投运。

2 一种可行的应急措施

某次机组检修,检修人员对6kV共箱母线进行抽查,设备未发现明显异常。修后机组开机前,天气晴朗且封母伴热装置一直处于投运状态,母线绝缘情况良好,达到投运要求。但机组开机过程中,天气变化下起小雨,运行人员复测绝缘时发现高公变低压侧绝缘只有0.5MΩ,不满足设备投运要求,绝缘问题将影响机组能否顺利并网。通过常规的处理方法对变压器中性点套管瓷瓶、接地电缆与6kV开关柜侧母线瓷瓶擦拭、干燥后复测绝缘仍未见好转后,检修人员需要尝试新思路应急解决母线绝缘问题。……