叶丽娟 张青
摘要:本文主要研究了对终端自停进行自动筛选的一种方法。按传统运维模式,终端自停需现场检查并在系统标识,效率较低。有别于传统终端运维方式,本文提到的技术措施通过对电表和终端的电压、电流、对应开关的状态进行判断,形成判定依据并输出到计量自动化系统上进行标识,能够极大的提高工作效率。能够在终端运维工作中帮助计量运维人员快速、准确定位真正的故障点,实现精准运维的目的。
关键词:智能终端故障自停电压、电流
Abstract: This paper mainly studies a method of automatic screening for terminal self-stop. In traditional O&M mode, the automatic shutdown of the terminal requires on-site inspection and identification in the system, which is inefficient. Different from the traditional terminal O&M mode, the technical measures mentioned in this paper can greatly improve the work efficiency by judging the voltage and current of the meter and terminal and the state of the corresponding switch, forming the judgment basis and outputting it to the metering automation system for identification. It can help the metering operation and maintenance personnel quickly and accurately locate the real fault point in the terminal operation and maintenance work, so as to achieve the purpose of accurate operation and maintenance.
Key Words: Intelligent terminal; Fault; Self-stop;Voltage; Electric current
为了提升终端远程抄表的准确性,需要运维人员通过现场运维对离线的终端进行处理,确保终端上线率。终端离线大致可以将其分为以下四类:一次回路故障、计量回路故障、终端或电表故障、用户自停。对于用户自行停电导致负控终端没有驱动电源离线的情况,这种不属于终端或计量回路本身的故障,仅需要现场核实并在计量自动化系统中予以标识,并不需要现场运维。为了提高工作效率,本文提供了一种技术措施快速排查筛选出用户自停的终端[1]。
1运维工作现状
1.1 运维工作步骤
目前,计量班组针对终端、电表故障等现象处理步骤主要如下。
(1)网上召测数据进行分析、排查。
(2)网上统计离线终端数。
(3)分析判断出哪些失压失流、无负荷及离线。
(4)去到现场运维,逐一核查故障点。
(5)得出设备故障、电压电流回路不正确、无信号以及用户自停等结论。
1.2影响采集成功率的因素
目前,用电信息采集系统普遍采用RS485通信(部分地区使用的是小无线通信方式)和移动GPRS无线通信的二级通信方式,高压用电信息采集系统的通信方式,其中任意级通信方式出现问题均会影响用电信息采集成功率。……