闵晶妍 陈红兵



摘要 准确、快速检测电网相位是并网变流器的关键技术,目前常用的闭环锁相技术普遍存在动态延时长、滤波算法复杂、在电网受谐波污染时锁相精度低等问题。针对上述不足,研究了降阶滤波器及其分序机理和实现方法,在此基础上,研究了基于降阶滤波器的锁相方法,并整定了环路滤波器的参数。实验结果表明,所研究的锁相技术在电网电压跳变的情况下,相位检测没有暂态过程,锁相精度不受电压幅值突变的影响;在电网中存在3次谐波电压时,锁相精度提高了21%;频率跳变不影响锁相过程和锁相精度,但是暂态过程约为20 ms,同时该锁相环还能检测单相电网的相位,较好地克服了常用的闭环锁相技术存在的问题。
关 键 词 降阶滤波器;分序算法;环路滤波器
中图分类号 TM46 文献标志码 A
Abstract The accuracy and rapidly detecting the phase of a grid is a key technology for grid-connected converters. There were some disadvantages in the common close loop PLL, such as a long dynamic response, complicated filter algorithms and low accuracy of the phase locked under distorted utility conditions. According to the above-mentioned disadvantages, the decomposing sequence method based on a reduce order filter, decomposing sequence mechanism and realization way have been analyzed. On that basis, the locked phase method based reduce order filter have been investigated. Parameters of the loop filter have been tuned. Lastly, the studied phase-locked technology has no transient response when the grid voltage dipped; Locked phase accuracy has been enhanced by 21% when the grid voltage component composes of the 3th harmonic wave voltage; The grid frequency fluctuation has no influence on locked phase accuracy and process, but there was a transient process of the 20ms. the investigated phase-locked technology can detect the phase of single-phase grid. The method has overcome the disadvantages of the common close loop PLL.
Key words reduce order filter; decompose sequence algorithm; loop filter
0 引言
准确、快速检测电网相位是并网变流器的关键技术。相位检测系统性能的优劣不仅关系到并网变流器的正常运行[1],而且还影响新能源电力系统的安全稳定[2]。因此,研究相位检测技术既有工程价值,也有学术意义。目前,相位检测技术分为2大类,即开环锁相技术和闭环锁相技术。
开环锁相技术没有调节过程,锁相过程短,这是开环锁相技术的优点。但是,对于电压严重畸变的电网,该方法不适合。闭环锁相技术稳态性能好、电网适应性能强,是当前研究、应用的主流技术。闭环锁相技术是运用反馈控制原理检测电网的频率和相位,它具备良好的幅值、相位和频率自适应能力。……