闫亚刚 刘璐 杨卫国 姚伟 包联霜 李忠富



摘 要:运行电站反馈结果显示,某隔离接地开关观察窗有裂纹。通过人、机、料、法、环等5个方面进行综合分析,笔者发现观察窗组装工器具的使用和极限尺寸导致的应力集中是造成观察窗裂纹的原因,并通过试验进一步验证了分析结果。研究表明,对观察窗进行设计结构优化,可以提高有机玻璃板强度,减小凸台应力聚集,进一步确保设备安全稳定运行。
关键词:观察窗;有机玻璃板;工器具;受力分析
中图分类号:TM595 文献标识码:A 文章编号:1003-5168(2021)09-0050-04
Abstract: The feedback results of the operating power station showed that there was a crack in the observation window of a certain isolation grounding switch. Through a comprehensive analysis of five aspects, including man, machine, material, method and ring, the author found that the use of observation window assembly tools and the stress concentration caused by the limit size were the causes of the observation window cracks, and the analysis results were further verified through experiments. Studies have shown that optimizing the design and structure of the observation window can increase the strength of the plexiglass panel, reduce the stress accumulation of the boss, and further ensure the safe and stable operation of the equipment.
Keywords: observation window;plexiglass panel;tools and instruments;force analysis
氣体绝缘全封闭组合电器(Gas Insulated Substation,GIS)是指把断路器、隔离开关、接地开关、电压互感器、电流互感器、母线、套管等按电气主接线的要求,依次连接组合成一个整体,并且全部封闭于接地的金属外壳内,壳体内一般充以0.4~0.6 MPa的绝缘气体,通常以SF6气体作为绝缘和灭弧介质。GIS具有结构小型化、安全性好、不受外部环境影响、安装周期短、检修周期长、安装调试容易和灭弧性能优秀等特点,在电力系统中得到广泛的应用,特别是在110 kV及以上的电力系统中,GIS设备已占主导地位。同时,GIS零部件多,结构复杂,而且对尺寸配合、工艺实施要求较高,设备运行过程中难免出现一些问题。近期,某电站反馈220 kV GIS隔离、接地开关动静触头的观察窗出现不同程度的裂纹现象,但未发生漏气。GIS内部充入高压力的绝缘气体,一旦观察窗发生爆破事故,就会对电网运行和设备本身造成重大损失,因此要对此进行研究分析,改进结构设计,确保电网安全可靠运行。……