【中图分类号】:TU998.1 【文献标志码】:C 【文章编号】:1008-3197(2025)03-53-05
【DOI编码】:10.3969/j.issn.1008-3197.2025.03.013
Numerical Simulation of Fire Smoke Spread from High-rise Residential Based on Pyrosim
LI Na,SUN Peng,LU Wenyuan
(The Instituteof Architectura Designand Research ofTaiyuan Universityof Technology,Taiyuan O3OO24,China)
【Abstract]:Conductafire review analysis ona high-rise residential accidentcase,anduse Pyrosim software to numerically simulate and restore the smoke spread situation,the sources of smoke in the shared front room,evacuation staircase,and electric pipewell were identified,and details,standards,and solutions that should be paid attention to in high-rise building fire engineering were proposed.
【Key words】: fire review;high-rise residential;smoke spread
高层建筑设计时会采取必要措施和方法来预防火灾的发生和减少火灾带来的危害,其中疏散楼梯间是火灾发生时建筑内人员安全疏散的通道,前室是消防救援队员开展火灾救援前整装、准备的安全区域。高层建筑的防烟系统通过自然通风和机械加压送风的方式,保障疏散楼梯间和前室不受火灾时产生的高温烟气影响,为人员疏散和火灾救援提供一个安全通道。
本文结合一起高层住宅的真实火灾案例,根据项目设计备案施工图纸、现场火调数据和Pyrosim数值模拟结果,对火灾时烟气在高层住宅安全疏散口处的流动规律进行数值模拟分析,为火灾时建筑内人员安全疏散和快速消防救援提供参考。
1现场概况
事故现场为一栋一类高层住宅楼,地下1层,地上32层,层高 2.9m ,总建筑高度约 92.8m ;标准层为东、西2个单元,每个单元有4户,设置剪刀楼梯和消防电梯。其中疏散楼梯间和合用前室采用自然通风系统,疏散楼梯间前室采用机械加压送风系统,屋顶设置加压送风机。见图1。

注:红色区域采用自然通风系统;黄色区域采用机械加压送风系统
事故起火原因为电管井内的供电元器件短路,造成电缆PVC绝缘护套燃烧,引燃周围其他可燃物;起火点位于东单元8层电管井内,火灾在电管井内竖向蔓延,8\\~32层电管井内电缆的PVC绝缘护套已燃烧殆尽,露出内部的银色铝制缆芯。
1.1防火门开关情况 ……p>