摘 要:文章介绍了地铁直流供电系统构成,直流1500V馈线开关的保护类型、保护范围,如何根据直流馈线开关所设保护初步判断故障点。直流馈线开关跳闸后的故障现象、类型,重点分析馈线开关重合闸不成功情况下如何用排除法寻找故障点,然后举例说明采用排除法在实际应用中遇到新的问题,以及提出建议,如何解决新的问题。

关键词:直流1500V馈线开关;保护;故障点;建议

中图分类号:TM643 文献标志码:A 文章编号:2095-2945(2018)18-0119-03

Abstract: This paper introduces the composition of the direct current (DC) power supply system for the subway, the protection type and protection range of the DC 1,500 V feeder switch, and how to determine the fault point based on the protection set by the DC feeder switch. The fault phenomena and types after DC feeder switch tripping are analyzed, and how to find the fault point by eliminating method under the condition of unsuccessful reclosing of feeder switch is analyzed emphatically. Then, some examples are given to illustrate the new problems encountered in practical application using the elimination method. Finally, suggestions on how to solve new problems are provided.

Keywords: DC 1500V feeder switch; protection; fault point; suggestion

1 地铁直流供电系统构成及保护配置

地铁直流供电系统主要由牵引降压变电所、架空接触网系统两部分组成,牵引降压变电所将来自110/33kV主变电站的交流33kV电压经降压、整流变为DC1500V后,通过直流开关柜向接触网供电。直流牵引供电系统接线示意图如图1所示:

地铁直流牵引系统是地铁列车运行的动力之源,其安全可靠运行是地铁安全、可靠运营的保证,在进行直流牵引供电系统的设计时,应综合分析系统的灵活性和可靠性,一方面应考虑地铁列车高密度运营的外部条件,另一方面应考虑当直流供电系统发生故障情况下,迅速切除故障点,同时通过相邻牵引电源及时恢复地铁列车的供电。

牵引变电所内的直流供电设备主要包括1500V直流开关柜、整流器柜、负极柜。针对可能的各种故障情况,直流供电系统配置了多种保护。

(1)直流馈线开关(馈出线柜):装设了大電流脱扣保护(直流快速断路器本体所具有的保护功能)、电流增量△I保护、电流上升率di/dt保护、定时限过电流保护、双边联跳等保护,各种保护相互配合,实现对接触网近端和远端短路进行保护。……

登录APP查看全文

猜你喜欢
保护建议
接受建议,同时也坚持自己
学生天地(2020年32期)2020-06-09 02:57:54
好建议是用脚走出来的
人大建设(2018年9期)2018-11-18 21:59:16
基于Web的非物质文化遗产土族盘绣电子商务平台的设计与实现
软件工程(2016年8期)2016-10-25 15:58:54
刍议增强林业生态环境保护的有效途
现代园艺(2016年17期)2016-10-17 08:49:07
浅谈遗址公园的保护
现代园艺(2016年17期)2016-10-17 07:58:52
反渗透长期停用保护方法的探索
建议答复应该
浙江人大(2014年4期)2014-03-20 16:20:16
日忧美军“保护”钓鱼岛能力 将强化攻击能力
环球时报(2013-07-27)2013-07-27 09:28:54
几点建议
中国火炬(2010年7期)2010-07-25 10:26:07