二次滤网自动控制系统PLC改进并纳入DCS监控

2018-12-29 08:11:02张向民
中小企业管理与科技·上旬刊 2018年10期

张向民

【摘 要】论文简述二次滤网工作过程,针对运行中存在的问题,对原控制系统提出了相应的改进方案,设计了PLC自动控制逻辑,在分散控制系统中进行了逻辑和画面组态,实现二次滤网的自动控制及远程监控,提高了二次滤网工况的稳定性、可靠性。

【Abstract】The paper briefly describes the working process of the secondary strainer. In view of the problems existing in its operation, the  corresponding improvement scheme to original control system is put forward. The automatic control logic of PLC is designed, and the logic and picture configuration are carried out in the decentralized control system. The automatic control and remote monitoring of the secondary strainer are realized, and the stability and reliability of the secondary strainer are improved.

【关键词】二次滤网;  PLC控制;  分散控制系统;  组态

【Keywords】secondary strainer; PLC control; decentralized control system; configuration

【中图分类号】F407.67                                    【文献标志码】A                                     【文章编号】1673-1069(2018)10-0161-02

1 引言

本钢发电厂的凝汽式汽轮发电机组及汽动鼓风机组承担着为本钢生产供电、供风的重要作用,机组循环水系统的良好工作是保证机组安全、稳定运行的重要一环,提高循环水的水质则是保证循环水系统良好工作的前提。为提高循环水的水质,在循环水泵的进口处安装固定拦污栅,一次滤网等过滤装置,对进水进行粗过滤;在循环水泵出口到凝汽器入口管道间安装二次滤网,再次对水进行细过滤;在凝汽器的水侧安装胶球自动清洗装置,对运行的凝汽器铜管内壁进行清洗,以保证凝汽器的换热效果。

本钢发电厂采用冷却水塔的循环式供水系统,其补给水来自本钢厂区地下供水管网,水源取自太子河水,由于河水污染日趋严重且水中杂物越来越多,加重了循环水过滤装置的负担。而一、二次滤网稳定工作是保证水质过滤的必要条件,尤其是二次滤网若不能稳定工作则会使水中的固体颗粒和悬浮物进入凝汽器堵塞铜管,使胶球清洗装置不能正常投用。若凝汽器铜管内壁结垢,传热恶化,会导致真空度下降,影响机组运行。……