某电厂500kV开关站线路分相电流差动保护简析

2021-08-10 05:50:16李忠佩
科技创新导报 2021年12期
关键词:动作故障

李忠佩

摘  要:线路差动保护从原理上是理想的一种保护方式,光纤分相电流差动保护借助于线路光纤通道,通过对电流的测量,实时地向对侧传递采样数据,同时接收对侧的采样数据,各侧保护利用本地和对侧电流数据按相进行差动电流计算。根据电流差动保护的制动特性方程进行判别,判为区内故障时动作跳闸,判为区外故障时保护不动作。

关键词:分相电流差动保护  PCS-931  CSC-103A  压板

中图分类号:TM773           文献标识码:A            文章编号:1674-098X(2021)04(c)-0098-03

Analysis on Phase Current Differential Protection of 500KV Switch Station Line in a Power Plant

LI  Zhongpei

(The Fourth Duty, No.3 Operation Division of China Nuclear Power Operation Management Co., Ltd., Jiaxing, Zhejiang Province, 314000  China)

Abstract: The line differential protection is an ideal protection mode in principle, with the help of optical fiber channel, the optical fiber split phase current differential protection transmits the sampling data to the opposite side in real time by measuring the current, and receives the sampling data from the opposite side at the same time. Each side protection calculates the differential current according to the phase by using the local and opposite side current data. According to the braking characteristic equation of the current differential protection, it is judged that the protection will trip when the fault is in the area, and the protection will not operate when the fault is out of the area.

Key Words: Split phase current differential protection; PCS-931; CSC-103A; Pressure plate

為规范华东电网500kV系统线路等双重化保护的应用方式,方便调试和运行维护,华东电网500kV系统第一套、第二套保护的定义中,关于线路保护条件[1]:保护原理优先级的定义,优先级从高到低依次为分相电流差动、方向高频、高频距离。我厂根据要求将主保护改造为分相电流差动保护。

1  分相电流差动保护

1.1 基本原理

分相电流差动保护的基本原理是根据线路在内部故障和外部故障时线路两端对应相的向量幅值和之间的比较来确定的[2]。

如图1系统中,当线路的电压不是很高,线路不是很长,即不考虑线路分布电容的影响时,可以采用不带制动量的原理,其判据方程为≥。但对于高压长距离输电线路的分相电流差动纵联保护来说,由于线路的分布电容电流大,并联电抗器电流、暂态过程中衰减非周期分量以及电流互感器饱和等原因,在线路外部短路时,不平衡电流很大,因此必须采用带有制动量的动作方程,才能保证保护不误动,即本文采用的,其中K表示制动系数(0

在外部故障时,|IM+IN|≈0,而|IM-IN|的幅值很大,动作方程不能满足。……