35kV变电站主变主保护动作及故障原因分析和解决对策

2018-05-07 07:05:28田富波
科技视界 2018年5期
关键词:解决对策

田富波

【摘 要】35kV变电站是煤矿供电系统中重要的组成部分,它担负着电能转换和电能重新分配的任务,而变电站中的主变压器更是其中主要设备之一,它的安全运行与否关系到整个电网的安全,对电网的安全和经济运行有着举足轻重的作用。本文针对因雷击引起变压器主保护动作和变压器内部绕组击穿等故障原因进行分析并提出解决的对策。

【关键词】主变保护动作;接地电流;小接地电流系统;单相接地故障;解决对策

中图分类号: TM772 文献标识码: A 文章编号:2095-2457(2018)05-0062-002

【Abstract】The 35kV substation is an important part of the coal mine power supply system. It is responsible for the task of power conversion and energy redistribution. The main transformer in the substation is one of the main equipments. Its safe operation is related to the entire The security of the power grid plays a decisive role in the safety and economic operation of the power grid. This article analyzes the causes of the main protection actions of the transformer and breakdown of the internal windings of the transformer due to lightning strikes, and proposes countermeasures.

【Key words】Main transformer protection action; Ground current; Small ground current system; Single-phase ground fault; Solution

0 引言

因煤矿大部分地處偏远山区,在煤矿供电系统中存在着供电线路长,安全等级低与及部分线路穿越高雷区等一系列突出问题,因此外部雷击导致主变主保护动作的现象时有发生,更是发生了因接地电流侵入变压器内部击穿高压侧绕组绝缘并造成绕组匝间短路的永久性故障,造成了全矿区跳闸停电的供电事故,给煤矿的安全生产带来了极为不利的影响。为了进一步提高供电系统的安全可靠性,积极分析故障原因和存在的问题,并在问题的基础上探讨解决措施与对策,无论是对于煤矿安全还是整个电网安全都有着重要的意义和价值。

1 主变故障的发生及现象

2016年6月30日,广平35kV东区变电站遭遇强雷击天气,14时50分左右2#主变(3150kVA,35kV/10kV)本体及开关重瓦斯动作、变压器差动保护动作导致主变两侧开关跳闸,造成全站失压。主变保护测控装置显示主变差动电流0.58A(整定启动值0.5A)、变压器本体及开关重瓦斯保护启动、2#主变油温告警,泄压阀启动,轻瓦斯未告警;……

登录APP查看全文

猜你喜欢
解决对策
硬笔书法教学问题及解决对策
戏剧之家(2016年20期)2016-11-09 23:53:22
国有企业行政管理中存在的问题和解决对策
电力综合自动化系统存在问题分析与解决措施
我国商业银行个人理财业务发展状况研究
时代金融(2016年23期)2016-10-31 11:38:08
关于我国商业银行个人理财业务的几点思考
国有企业人才招聘模式存在问题及解决对策
浅析农村宅基地登记发证过程中遇到的问题及解决对策
余额宝的理财方式存在的问题及解决对策
论中小型企业成本会计核算及分析研究
对影响我国注册会计师审计独立性的原因及对策的研究
商(2016年27期)2016-10-17 05:38:10